Open Access Open Access  Restricted Access Subscription or Fee Access

Solar PV Integrated UPQC Using Fuzzy Logic Controller for A Grid Connected System

S. Kavitha, Dr. SP. Umayal, M. Swathisriranjani

Abstract


This paper introduces optimal utilization of solar photovoltaic array integrated PV-UPQC-S by modified p-q theory based control for clean energy generation along with power quality improvement. UPQC is designed by the integration of series and shunt VSCs sharing a common DC bus capacitor. Voltage disturbance like sag, swell, unbalance and harmonics are being compensated by UPQC along with mitigation of source current harmonics. Series VSC simultaneously delivers active and reactive power using theory of power angle control of UPQC to coordinate load reactive power and hence named as UPQC-S. The fundamental frequency positive sequence (FFPS) components of voltages at PCC are extracted using generalized cascaded delay signal cancellation (GCDSC) technique to generate reference signals using p-q theory based control for the PV-UPQC-S. This helps in control of distorted PCC voltages. The series voltage source converter (VSC) shares a part of the reactive power of the load even under nominal grid conditions, thereby reducing the rating of shunt VSC. The PV array is integrated at the DC-bus of the UPQC, provides a part of active load power thus reducing demand on the supply system. The DC voltage is maintained constant using Fuzzy Logic Controller.  The shunt and series reference signals derived from the control algorithm and sensed signals are injected into FLC to generate switching signals. The proposed system can work under multiple disturbance such as irradiation variation, PCC voltage disturbance and harmonics occurring simultaneously. The dynamic performance of modified p-q theory based PV-UPQC-S is verified by simulating the system in Matlab-Simulink with combination of linear and nonlinear loads.


Keywords


Power Quality, UPQC-S, Solar MPPT, GCDSC, p-q Theory, Series Compensation, Shunt Compensation.

Full Text:

PDF

References


L. F. de Oliveira Costa and J. M. de Carvalho Filho, “Electrical power quality and the challenges faced by power assemblies applications in petrochemical industry, ”IEEE Trans. Ind. Appl., vol. 52, no. 5, pp. 4495– 4502, Sept 2016.

A. Banerji, S. K. Biswas, and B. Singh, “Enhancing quality of power to sensitive loads with microgrid,”IEEE Trans. Ind. Appl., vol. 52, no. 1, pp. 360–368, Jan 2016.

H.Hafezi, G.DAntona, A.Ded, D.D.Giustina, R.Faranda, and G. Massa, “Power quality conditioning in LV distribution networks: Results by field demonstration” IEEE Transactions on Smart Grid, vol. 8, no. 1, pp. 418–427, Jan 2017

V. Khadkikar and A. Chandra, “A novel structure for three-phase fourwire distribution system utilizing unified power quality conditioner UPQC,”IEEE Trans. Ind. Appl., vol. 45, no. 5, pp. 1897–1902, Sept 2009.

V. Khadkikar, “Enhancing electric power quality using UPQC: A comprehensive overview,” IEEE Trans. Power Electron., vol. 27, no. 5, pp. 2284–2297, May 2012.

B. B. Ambati and V. Khadkikar, “Optimal sizing of upqc considering va loading and maximum utilization of power-electronic converters,” IEEE Trans. Power Del., vol. 29, no. 3, pp. 1490–1498, June 2014.

V. Khadkikar and A. Chandra, “UPQC-S: A novel concept of simultaneous voltage sag/swell and load reactive power compensations utilizing series inverter of UPQC,”IEEE Trans. Power Electron., vol. 26, no. 9, pp. 2414–2425, Sept 2011.

S. Devassy and B. Singh, “Enhancement of power quality using solar pv integrated UPQC,” in39th National Systems Conference (NSC), Dec 2015, pp. 1–6.

S. Devassy and B. Singh, “Modified p-q theory based control of solar PV integrated UPQC-S,” in IEEE Industry Applications Society Annual Meeting, Oct 2016, pp. 1–8.

H. Akagi, E. Watanabe, M. Aredes, Instantaneous Power Theory and Applications to Power Conditioning. New Jersey: Wiley, 2007.

P. Kanjiya, B. Singh, A. Chandra, and K. Al-Haddad, “’SRF Theory Revisited’ to control self-supported dynamic voltage restorer (dvr) for unbalanced and nonlinear loads,” IEEE Trans. Ind. Appl., vol. 49, no. 5, pp. 2330–2340, Sept 2013.

R. S. Herrera and P. Salmeron, “Present point of view about the instantaneous reactive power theory,” IET Power Electronics, vol.2, no. 5, pp. 484–495, Sept 2009.

Y. F. Wang and Y. W. Li, “Three-phase cascaded delayed signal cancellation pll for fast selective harmonic detection,” IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1452–1463, April 2013.

S. Golestan, F. D. Freijedo, A. Vidal, A. G. Yepes, J. M. Guerrero, and J. Doval-Gandoy, “An efficient implementation of generalized delayed signal cancellation PLL,” IEEE Trans. Power Electron., vol. 31, no. 2, pp. 1085–1094, Feb 2016.

M. de Brito, L. Galotto, L. Sampaio, G. de Azevedo e Melo, and C. Canesin, “Evaluation of the main MPPT techniques for photovoltaic applications,” IEEE Trans. Ind. Electron., vol. 60, no. 3, pp. 1156–1167, March 2013.


Refbacks

  • There are currently no refbacks.


Creative Commons License